1 DESCRIPTION AND PRODUCTS

1.1 PURPOSE METER

1.1.1 IPD-10 is designed to measure tangent tg & delta dielectric loss; and capacitance high-voltage insulation C with maintenance, repair, adjustment, testing different energy objects as in their place of installation, and in laboratories, and also for measuring the dielectric loss tangent and capacitance various electric insulating materials.

1.1.2 The FPI-10 is made by meeting the requirements of GOST 22261 for electronic measuring devices group 4.

1.2 operating conditions

1.2.1 FPI-10 has the following normal conditions of use :

  • ambient temperature, & deg; C 20 & plusmn; 5;
  • relative humidity,% 30 & ndash; 50;
  • atmospheric pressure, kPa ( mm Hg) 84 & ndash;.. 106 (630 & ndash; 795);
  • mains frequency, Hz 50 & plusmn; 1;

    1.2.2 IPD-10 for operating under the following operating conditions of use:

    • ambient temperature, & deg; C from minus 10 to plus 40;
    • relative humidity, 90% etc. and 30 & deg; C;
    • Atmospheric Pressure, kPa (mm. Hg. v) 70 & ndash;. 106,7 (537 & ndash; 800);
    • mains frequency, Hz 50 & plusmn; 1 or 54 & plusmn; 0.2 Hz;

      1.2. 3 Limit conveying conditions:

      • ambient temperature, & deg; C, from minus 50 to plus 50;
      • relative humidity,% 95 at 30 & deg; C;
      • atmospheric pressure, kPa (mm Hg.). 70 & ndash; 106,7 (537 & ndash; 800);
      • tossing:
      • bpm 80 & ndash; 120;
      • maximum acceleration in m / s2 30;

        1.2.4 Operation of products can be made by one operator among electrical staff to examine the document, after training in practical use the product, and having a group of safety in installations with a voltage over 1,000 V not less than the third

        & nbsp;.

        1.3 SPECIFICATION

        & nbsp;

        1.3.1 IPD-10 & ndash; dual-band meter insulation parameters. IPI-10 provides a measurement of the dielectric loss tangent and capacitance. Specifications are given in the Table. . 1

        & nbsp;

        Table 1

        first range (& laquo; INPUT 1 & raquo;)

        A range measuring dielectric loss tangent of 1) < / sup>

        5 . 10 -4 to 0,3;

        tolerable -limit absolute basic error in the measurement of the dielectric loss tangent for the total capacitance of the measuring range when the test voltage frequency:

        50Hz

        + (5 10 -4 + 0,05 tg & delta;.)

        54 Hz

        + (1 . 10 -3 + 0,13 tg & delta;)

        A range of capacitance measurement at the test voltage:

        10 kW

        from 25 pF to 30 000 pF;

        5 kV

        From 50 pF to 60 000 pF;

        - maximum permissible basic error in measuring the capacitance at the frequency:

        50Hz

        + (0,5 + 0,03 pF Cx);

        54 Hz

        + (0,5 + 0,04 pF Cx);

        - operating voltage range < td>

        1 to 10 kV;

        - maximum permissible relative error in the measurement of RMS voltage at frequency

        50Hz

        + 3%; < / tr>

        54 Hz

        + 3%.

        force a current through the measurement object A 2)

        0 to 0,150

        & nbsp;

        1) -izmeritel recalculates the dielectric loss tangent as measured at a frequency of 54 Hz to 50 Hz;

        2 ) - is for reference

        & nbsp; . The second range (& laquo; INPUT 2 & raquo;)

        < td >

        - maximum permissible relative error in the measurement of RMS voltage at frequency

        & nbsp;

        A range measuring dielectric loss tangent of 1)

        1 . 10 -3 to 0,3;

        tolerable -limit absolute basic error in the measurement of the dielectric loss tangent for the total capacitance of the measuring range when the test voltage frequency:

        50Hz

        + (1 10 -3 + 0,1 tg & delta;.)

        54 Hz

        is not normalized

        A range of capacitance measurements at test voltage:

        10 kV

        of 30000 pF to 1,5 & middot; 10 6 pF;

        5 kV

        by 60,000 pF to 3 & middot; 10 6 pF

        - maximum permissible basic error in measuring the capacitance at the frequency:

        50Hz

        + (2 pF Cx + 0.05);

        54 Hz

        It is not normalized

        - operating voltage range

        1 to 10 kV;

        50Hz

        < p> + 3%;

        54 Hz

        + 3%.

        force a current through the measurement object A 2)

        to 5

        & nbsp;

        1) -izmeritel recalculates the dielectric loss tangent measured at the frequency 54 Hz to 50 Hz;

        2 ) - given for reference .

        & nbsp; 1.3.2 limit of tolerable additional measurement error caused by changes in ambient temperature from normal (20 & plusmn; 5 & deg; C) to either within the working area, does not exceed half the maximum permissible primary measurement error for every 10 degrees. . Temperature changes

        1.3.3 IPD-10 allows measurement of & laquo; normal & raquo; / & laquo; direct & raquo; and & laquo; inverted & raquo; / & laquo; inverted & raquo; measurement schemes that provides a measure of insulation objects parameters as with isolated or grounded pin.

        1.3.4 IPD-10 provides an output of measurement results on the liquid crystal display (LCD) display unit. The connection between the high-voltage measuring unit and the display unit is carried on a radio channel in the frequency range 845-945 MHz, with 1 mW output power of the transmitter at a distance of 5-7 m.

        1.3.5 Image numbers and symbols on the display distinguishably distance not less than 0.8 m at an external illuminance of 10 to 1,000 lux.

        1.3.6 IPD-10 in normal operating conditions and the application is ready to operate for no more than 1 minute after switching.

        1.3.7 The duration of the meter is determined by power consumption used by the electrochemical battery. When the battery capacity of 1800 mA & middot; hour operation time is not less than 8 hours

        1.3.8 MTBF for the operating conditions of application of at least 4000 h

        1.3.9 average period.. service meter & ndash; at least 8 years

        1.3.10 Dimensions and weight of the meter components shown in Table 1

        & nbsp;..

        1.4 PACKAGE

        IPI-10 supplied completeness, shown in table 1.

        table 1

        № < / p>

        Name

        part

        designation

        Max

        dimensions, mm < p> Weight,

        kg

        Note

        1

        < p> unit HV

        IPI-10-DB

        1

        < p> & AElig; 240 x 300

        3

        & nbsp;

        4

        The display unit

        IPI-10MI

        1

        90h186h42

        0,3

        & nbsp;

        5

        charger

        9-12V,

        300-900 mA

        2

        < p> & nbsp;

        & nbsp;

        & nbsp;

        6

        Stand insulation constant prices

        PI 10

        1

        & nbsp; < / p>

        & nbsp;

        & nbsp;

        < p> 7

        cable set measurement:

        & nbsp;

        & nbsp;

        IR-1

        IC-30

        & nbsp;

        1,5 m

        30 m

        & nbsp;

        & nbsp;

        & nbsp;

        8

        Measuring the insulation value high-FPI-10.

        operating Instructions

        IPI-10.00.00RE

        FPI-10 00.00.00RE

        1

        & nbsp;

        & nbsp;

        & nbsp; < /p>

         

        1.5 DEVICE METER

        & nbsp;

        1.5.1 IPD-10 the principle of operation is a vector measuring complex impedance parameters (vektormetr).

        The composition of the meter includes a high voltage unit, display unit.

        The connection between the high unit and the display unit is carried out by radio .

        1.5.2 high voltage Schematic block diagram is shown in Figure 1, and its appearance and design & ndash; Figures 2 and 3.

        1.5.3 Appearance IPI-10MI display unit is shown in Figure 4.

        The display unit is configured in a plastic shockproof type KM103 housing. On the front side are placed - the LCD screen and the controls and indicators described in the caption label. The side wall is jack adapter charger (9-12V, 300-900 mA).

        On the back wall there is an access cover to the compartment supply. Power IPI-10MI made from four cylindrical nickel-metal hydride batteries of AA size 1.2 voltage and capacity of 1800-2500 mA & times; h

        1.6 METER OPERATION <. p> 1.6.1 this section describes the operation of

        1.6.2 FDI FDI-10-meter 10 is a set of electronic devices, measuring the four parameters simultaneously:.

        - load current ( complex quantity);

        - load voltage (scalar);

        - load voltage (vector quantity);

        - test voltage frequency

        From these data, the electronic device disposed in the high voltage unit calculates the capacitance Cx of the test object and tangent tg & delta dielectric loss; and transmits the data by radio to the display unit, where they are displayed on the screen.

        1.6.3 Depending on the characteristics of the test object to measure the losses in the insulation can be used the so-called & Laquo; inverted & raquo; (& Laquo; inverse & raquo;) test circuit, or & laquo; direct & raquo; (& Laquo; normal & raquo;) (Figures 5 and 6)

        In & laquo;. Inverted & raquo; circuit testing one of terminals grounded object, in & laquo; direct & raquo; - both the conclusion of the object under potential .