Installing a universal breakout VGA-10
|
1. PURPOSE h3>
1.1 Installation breakout universal VGA 10 (hereinafter in the text & ndash; TOS-10) is designed to test the insulation of electrical equipment and materials alternating sinusoidal voltage of 50 Hz and the rectified voltage of negative polarity, regulated within 0 -10 kV with an output current to 100 mA p>
Scope & ndash; electrical engineering and energy. p>
Due to an increased output current setting can be used to test alternating voltage winding insulation of large electrical machines. C may be successfully used for the test safeners to the respective voltage (glove, etc.), as well as to charge the capacitive energy storage. P>
1.2 unit is designed for operation indoors or under a canopy at operating temperatures air from plus 5 & deg; C to + 40 & deg; C, relative humidity of 80% at a temperature of 20 & deg; C and atmospheric pressure 84,0 & ndash; 106.7 kPa (630 & ndash; 800 mm Hg...) P>
1.3 Power & ndash.; single phase sinusoidal alternating voltage of 220 & plusmn; 20 V, frequency 50 & plusmn; 1Hz p>
1.4 Installation operated by one operator with the right work on installations with voltages above 1000V p>
& nbsp;.. p>
2. SPECIFICATIONS h3>
2.1 The limits of the output voltage setting, kV 1; 3; 10 p>
2.2 The above relative installation error and measurement output p>
voltage,%, no more than - 3 p>
2.3 maximum output current, mA - 100 p>
2.4 The above relative current measurement error,%, no more than - 3 p>
2.5 threshold current protection mA - 102 & plusmn; 2 p>
2.6 power consumption, V. A not more than 1000 p>
2.7 Overall dimensions, the control unit - 320h200h355 high voltage unit - 315h290h410 p>
2.8. Weight, not more than: p>
control unit - 15 p>
high voltage unit - 25 p>
2.9. Time of continuous operation at maximum power, hour - 8 p>
2.10. The average life of the product, years & ndash; . 6 p>
NOTE: strong> kilovoltmeters installation measures the alternating voltage - the rms value, rectified on & ndash; voltage amplitude value. p> Milliammeter AC measures the current value on the aligned p> secondary (srednevypryamlennoe) current value. p>
Documentation for download of the device not available